Material: Al conductor/XLPE insulation/SWA/PVC sheath
Rated voltage (Uo/U): 0.6/1kV
Number of cores: single-core, two-core, three-core, four-core, five-core, three core and earth (three primary conductor and one neutral conductor), three core and two (three primary conductor and two neutral conductor), four core and earth (four primary conductor and one neutral conductor)
Highest allowed operating temperature of conductor for long-term working is 90°C
In short-circuit (maximum long-term is not more than 5 seconds)
Highest temperature for conductor is no more than 250°C
DC resistance of conductor complies with stipulations of BS 6724 or IEC 60502-1
Environment temperature should not lower than 0°C when lay, otherwise should be preheated
Cable is laid without horizontal drop limit
Working frequency voltage test: 2.5Uo + 2kV/5 minutes without puncture
Partial discharge test: discharge volume should not more than 10pC under 1.73Uo for cable
Certifications: ISO and CCC
Manufacture under BS 6724 or IEC 60502-1 and IEC 60228
Applications:
Used to transmit and distribute power in power transmission and distribution system of 1kV
Generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable and in partial replace of PVC insulated power cable